Gillette SENTRY-PRO SPD SERIES 85-165 KW

Gillette SENTRY-PRO SPD SERIES 85-165 KW

Features
  • HOUSING: Rust proofed steel enclosure with weather and sound protection, easy service access thru large lockable doors.
  • CONTROLLER: Our "SENTINEL-SCOUT" controller is standard equipment on all liquid cooled 1800 RPM gen-sets. We urge you to view this separate features page to learn of the multitude of engine-generator protectors, upgrade to "SENTINEL III", plus our new NFPA style ANNUNCIATOR and the new "SENTINEL IV" controller for tele-communication applications.
  • MICROPROCESSOR: This digital controller monitors normal utility power constantly, and when normal power fails, you have emergency power within 10 seconds. No failure-prone mechanical relays are allowed in this all digital circuitry.
  • CONTROL PANEL: Large and spacious for easier installation connections. Panel door is lockable.
  • INTERIOR AIR DUCTS: Clean fresh air is ducted into the housing. The heat generating items (engine and muffler) are ducted out of the housing. This results in the coolest operating gen-set, available.
  • MUFFLER: Mufflers are used for additional silencing. Exhaust outlet is directed straight up for better safety. Critical and residential mufflers are available as an option, for even more exhaust silencing.
  • AUTOMATIC TRANSFER SWITCH (SUPPLEMENTAL EQUIPMENT): Designed to automatically switch failed utility power out and emergency generator power in, and connect to your loads. This electrically operated, mechanically held switch is UL-1008 certified and has the following features: Engine automatic exerciser, will start and run your gen-set once per week, time delay to start (avoids nuisance starts with common power glitches), time delay for engine cool down before final stop, LED annunciator lights mounted on ATS front cover for showing normal power or emergency power in use, NEMA 1 metal enclosure (for inside installation) or NEMA-3R enclosure (for outdoor installations), and 100 thru 1200 Amp capacity at 240 Volts, 1 phase, or 208, 220, 240, and 480 Volts, 3 phase to match most incoming utility power. The automatic transfer switch is a separate part of the Sentry-Pro standby package, and it is sold separately due to the many choices of different styles and designs of ATS Systems, available to our customers.





Technical Specifications

DIESEL GENERATOR MODELS WITH SINGLE PHASE KW RATINGS
1 PHASE MODELS SPJD-850-1 SPJD-1050-1 SPJD-1300-1 SPJD-1650-1
Max Output KW @ 1 Phase, 1.0 P.F. 85.0 105.0 125.0 165.0
Standby Output KW @ 1 Phase, 1.0 P.F. 78.0 100.0 120.0 160.0
3 PHASE MODELS SPD-850-3 SPD-1050-3 SPD-1300-3 SPD-1650-3
Max KW/KVA Output @ 3 Phase, .8 P.F. 85.0/106.0 105.0/131.0 130.0/162.5 165.0/206.0
Standby KW/KVA Output @ 3 Phase, .8 P.F. 80.0/100.0 100.0/125.0 125.0/156.0 160.0/200.0
ENGINE SPECIFICATIONS
Engine JOHN DEERE
Engine HP 126 158 198 237
Engine Cyl. 4 4 6 6
Engine RPM 4 POLE, 1800 RPM
Engine Piston Area 4.0L. 4.0L. 6.0L. 6.0L.
Engine Induction System
Turbo-charged induction system with charged air cooler (CAC).
Available Engine Muffler Types Open (No Enclosure) has industrial muffler for normal exhaust silencing.
Standard hosuing has residential muffler for average exhuast silencing.
Super-silent housing has a residential muffler for above average exhaust silencing.
Engine Fuel Above 32°F = #2D diesel fuel: Below 32°F = A 50-50 mix #1D and #2D diesel fuel. It is recommended to use a battery heater and fuel heater for temperatures below 32°F.
CONTROL SPECIFICATIONS
Controller "SENTINEL-SCOUT" digital controller with engine and genrator star-stop controlls.
Engine & Generator Auto-Shutdown Protectors Low oil, over-speed, high temperature and over-crank failure shutdown protection. Over-crank has (3) seperate starting attemps before shutdown.
Meter Package Hour meter included. This system included the "SENTINEL III" digital controller for full metering and control.
Circuit Breaker Optional equipment due to the variety of requirements at installation points. Please contact us for the options available for your needs.
Battery Charger Standard Equipment.
COMPLETE GENERATOR SET SPECIFICATIONS
Weather Housing All housings are made of rust-proofed galvanized steel and suitable for all weather conditions. Air Baffles and sound proof foam allows superior noise level reduction.
Open Set Dim (LxWxH)  88" X 48" X 50" 98" X 48" X 53"
Std. Housed Set Dim (LxWxH)  108" X 48" X 68" 118" X 48" X 68"
S.S. Housed Set Dim (LxWxH)  128" X 48" X 68" 138" X 48" X 68"

Available Accessories (SPECIAL ACCESSORIES AVAILABLE UPON REQUEST)

NOTES:

Technical specifications are subject to change. Please contact us to verify specifications.